Key technical performances | Standard | IEC 60502 | ||||||
Voltage classes | 6/10(12)kV | 8.7/15(17.5)kV | 12/20(24)kV | 18/30(36)kV | ||||
Partial discharge test at ambient temperature | 10kV,<10pC | 15kV,<10pC | 20kV,<10pC | 30kV,<10pC | ||||
AC withstand voltage test | 27kV 5min | 39kV 5min | 54kV 5min | 81kV 5min | ||||
Impulse voltage withstand | ±75kV each polarity 10 times | ±95kV each polarity 10 times | ±125kV each polarity 10 times | ±170kV each polarity 10 times | ||||
Selection table | Screen cable Connector | Screen Rear cable Connector | Cable Insulation OD(mm) | Cable Conductor Cross-section(mm2) | ||||
6/10(12)kV | ||||||||
GSFC-12-630A-A | GSRC-12-630A-A | 16.5mm-20.9mm | 70mm²-95mm² | |||||
GSFC-12-630A-B | GSRC-12-630A-B | 20.3mm-24.3mm | 120-mm²-185mm² | |||||
GSFC-12-630A-C | GSRC-12-630A-C | 24.7mm-29.5mm | 240mm²-300mm² | |||||
GSFC-12-630A-D | GSRC-12-630A-D | 29.5mm-36.3mm | 400mm²-500mm² | |||||
GSFC-12-630A-E | GSRC-12-630A-E | 34.5mm-41.5mm | 630mm² | |||||
8.7/15(17.5)kV | ||||||||
GSFC-17.5-630A-A | GSRC-17.5-630A-A | 16.5mm-20.9mm | 25mm²-50mm² | |||||
GSFC-17.5-630A-B | GSRC-17.5-630A-B | 20.3mm-24.3mm | 70mm²-120mm² | |||||
GSFC-17.5-630A-C | GSRC-17.5-630A-C | 24.7mm-29.5mm | 150mm²-185mm² | |||||
GSFC-17.5-630A-D | GSRC-17.5-630A-D | 29.5mm-36.3mm | 240mm²-400mm² | |||||
GSFC-17.5-630A-E | GSRC-17.5-630A-E | 34.5mm-41.5mm | 500mm²-630mm² | |||||
12/20(24)kV | ||||||||
GSFC-24-630A-A | GSRC-24-630A-A | 16.5mm-20.9mm | 35mm²-50mm² | |||||
GSFC-24-630A-B | GSRC-24-630A-B | 20.3mm-24.3mm | 70mm²-95mm² | |||||
GSFC-24-630A-C | GSRC-24-630A-C | 24.7mm-29.5mm | 120mm²-185mm² | |||||
GSFC-24-630A-D | GSRC-24-630A-D | 29.5mm-36.3mm | 240mm²-300mm² | |||||
GSFC-24-630A-E | GSRC-24-630A-E | 34.5mm-41.5mm | 400mm²-500mm² | |||||
18/30(36)kV | ||||||||
GSFC-36-630A-A | GSRC-36-630A-A | 25.2mm-30.2mm | 50mm²-95mm² | |||||
GSFC-36-630A-B | GSRC-36-630A-B | 30.2mm-35.9mm | 120mm²-185mm² | |||||
GSFC-36-630A-C | GSRC-36-630A-C | 35.9mm-41.2mm | 240mm²-300mm² | |||||
GSFC-36-630A-D | GSRC-36-630A-D | 41.2mm-44.5mm | 400mm²-500mm² | |||||
*NOTE: 1. Cable insulation outer diameter is one of the prerequisite for Cable accessories selection. 2. The connector suit for bushings according to EN 50181, connection type C. | ||||||||
ordering information | Ordering description | Specify details as follows (for example, GSFC 24kV/3C 70mm CWS,Alu Cable) | ||||||
Screen Type: CWS or CTS | ||||||||
Armor Type: SWA or STA |